630 kVA tekanan vakum impregnated trafo-11 / 0,55 kV|Afrika Kidul 2025

630 kVA tekanan vakum impregnated trafo-11 / 0,55 kV|Afrika Kidul 2025

Nagara: Afrika Kidul 2025
Kamampuh: 630kVA
tegangan: 11/0.55kV
Fitur: kalayan kipas sareng tingkat insulasi H
Kirim surélék Panalungtikan

 

 

630 kVA vacuum pressure impregnated transformer

Distribusi Daya Smart, Masa Depan Héjo - Ngabuka Transformers Kering Berliku pikeun Kelestarian!

 

 

01 Umum

1.1 Pedaran Proyék

The 630 kVA bubuka pungkal tipe garing trafo ieu dikirimkeun ka Afrika Kidul di 2025. The dipeunteun kakuatan tina lawang pungkal tipe garing trafo nyaeta 630 kVA kalawan AN / AF cooling, tegangan primér nyaéta 11 kV kalawan ± 2 * 2.5% rentang ngetok (NLTC), tegangan sekundér 0.55kV, aranjeunna ngawangun grup vektor Dyn1.

Opening Winding Dry Type Transformer kami direkayasa pikeun pagelaran anu unggul, ngagabungkeun téknologi canggih sareng konstruksi anu kuat pikeun nyumponan kabutuhan kakuatan industri sareng komérsial. Nampilkeun pangendali suhu anu cerdas, éta ngajamin manajemén termal anu optimal, bari diwangun-kipas cooling ningkatkeun dissipation panas pikeun efisiensi konsisten sanajan dina beban beurat.

Dirancang kalayan insulasi Kelas H, trafo ieu tahan -lingkungan suhu luhur, ngarojong naékna suhu 100K pikeun operasi jangka panjang-anu dipercaya. Cocog sareng catu daya 110V, éta nyayogikeun transformasi tegangan anu stabil kalayan leungitna énergi minimal.

Idéal pikeun otomatisasi industri, sistem énergi anu bisa dianyari, sareng infrastruktur kritis, trafo tipe -kering kami nawiskeun operasi gratis-pangropéa, kaamanan ditingkatkeun (teu aya résiko kahuruan), sareng kinerja ramah lingkungan -(teu aya émisi minyak atanapi toksik). Ningkatkeun ka solusi kakuatan anu langkung pinter, langkung tahan banting ayeuna!

 

 

 

1.2 Spésifikasi Téknis

630 kVA VPI tipe garing spésifikasi trafo jeung lambar data

Dihaturkeun ka
Afrika Kidul
Taun
2025
Tipe
Buka pungkal tipe garing trafo
Bahan inti
Lambaran baja silikon berorientasi gandum
Standar
IEC60076
Dipeunteun Power
630kVA
Frékuénsi
50 HZ
Grup vektor
Dina11
Fase
3
Tipe Cooling
ONAN/ONAF
Tegangan primér
11 kV
Tegangan sekundér
0,55 kV
Bahan gulung
alumunium
Impedansi
6%
Ketok Changer
NLTC
Ngetok Rentang
± 2*2,5% @ sisi primér ku ngetok Tumbu
Taya Beban Loss
1.1KW
Dina Beban Loss
8.3KW
Tingkat insulasi
H

 

 

1.3 Gambar

630 kVA VPI tipe garing trafo diagram gambar jeung ukuran.

vacuum pressure impregnated transformer diagram vacuum pressure impregnated transformer nameplate

 

 

02 Pabrikan

2.1 Inti

Trafo tipe garing -bukaan ngagulung gaduh inti laminasi baja silikon -perméabilitas luhur anu ngalaman perlakuan annealing presisi pikeun ngaleutikan leungitna sirkuit magnét. Inti ngadopsi struktur stacking stepped pikeun éféktif ngurangan karugian eddy arus, digabungkeun jeung téhnologi clamping husus pikeun mastikeun sepi, noise -operasi bébas.

 high-permeability silicon steel laminated core

 

2.2 Ngagulung

vacuum pressure impregnated transformer aluminum winding

Trafo ieu gaduh insulasi -kawat alumunium anu katepatan sareng insulasi multi-lapisan SHS (Super Heat-Sinthetic), sanggup nahan hawa nepi ka 220 derajat . Desain ventilasi kabuka -na inovatif mastikeun dissipation panas optimal bari ngajaga kinerja termal Kelas H (naékna suhu 100K). Struktur pungkal ngagabungkeun stabilitas mékanis bertulang kalawan kakuatan diéléktrik alus teuing, nawarkeun résistansi unggulan ka shock termal, Geter sarta ngurangan parsial.

 

2.3 Majelis ahir

1) Precision mounting of SHS-insulated coils onto CRGO cores; 2) Stepped-lamination upper yoke installation with 15-20kN/m clamping force; 3) install cooling fans and PT100 smart temperature controller (150℃ alarm/180℃ trip); 4) install terminal connections passing 5000V insulation tests (>1000MΩ).

final assembly of vip dry transformer

 

 

03 Nguji

No.

Item tés

Unit

Nilai ditampa

Nilai diukur

kacindekan

1

Pangukuran résistansi pungkal

/

Laju unbalance lalawanan maksimum

Rintangan garis: Kurang atanapi sami sareng 2%

HV (garis)

LV (garis)

Lulus

0.29%

0.84%

2

Ngukur rasio tegangan jeung pariksa kapindahan fase

/

Kasabaran rasio tegangan dina ngetok poko: ± 1/10

simbol sambungan: Dyn11

-0.02% ~ 0.13%

Dina11

Lulus

3

Pangukuran Impedansi Sirkuit -Pondok sareng Leungitna Beban

/

kW

kW

t: 145 darajat

Z%: nilai diukur

Pk: nilai diukur

Pt: nilai diukur

6.22%

4.745

6.485

Lulus

4

Pangukuran Taya-Beban Rugi sareng Arus dina 90% sareng 110% tina tegangan dipeunteun

/

kW

I0 :: nyadiakeun nilai diukur

P0: nyadiakeun nilai diukur

90% Ur

0.36

0.978

Lulus

100% Ur

0.40

1.087

110% Ur

0.44

1.195

5

Tes Tegangan Terapan

/

HV: 35kV 60s

LV: 3kV 60s

Taya runtuhna tegangan test lumangsung

Lulus

6

Ngainduksi tegangan tahan Test

/

tegangan dilarapkeun (kV):

2 Ur

tegangan induksi (kV): 1.1

Lilana (s):40

Frékuénsi (HZ): 150

Taya runtuhna tegangan test lumangsung

Lulus

7

Uji discharge parsial

pC

Tingkat maksimum sékrési parsial kedahna 10 pC

<10

Lulus

 

630 kVA vacuum pressure impregnated transformer test
630 kVA vacuum pressure impregnated transformer fat

 

 

04 Bungkusan sareng Pangiriman

4.1 Bungkusan

Trafo tipe -garing dibungkus dina peti kayu anu kuat sareng bantalan jero pikeun transportasi anu aman. Sadaya komponén, kalebet pangontrol suhu sareng kipas, tos dipasang sateuacana-sabagé unit lengkep. Bagian luarna jelas ditandaan ku parentah penanganan, nyadiakeun kalembaban anu bisa dipercaya jeung panyalindungan shock pikeun -pengiriman trafo jarak jauh.

dry type transformer packing

 

4.2 Pangiriman

dry type transformer shipping

Trafo tipe garing pungkal bukaan bakal dikirimkeun CIF Durban Port dina peti kayu buktina -shock. Hargana nyertakeun asuransi laut sareng beberesih adat ékspor, sedengkeun formalitas impor bakal diurus ku panarima. Kirimanna ngajaga kalembaban/suhu anu ketat saluyu sareng standar anti-anti korosi internasional pikeun angkutan laut.

 

 

05 Loka jeung Ringkesan

Minangka solusi efisiensi-luhureun pikeun pangiriman jeung distribusi daya, Opening Winding Dry Type Transformer kami nganteurkeun kaandalan anu langgeng pikeun sektor industri, tanaga, jeung infrastruktur ngaliwatan desain -kabuka anu inovatif, manajemén termal unggul, sareng insulasi anu kuat. Ngagabungkeun pangropéa-operasi bébas, konstruksi ramah lingkungan-, jeung kontrol suhu calakan, éta unggul dina aplikasi nuntut bari ngarojong tujuan énergi lestari. Mitra sareng kami pikeun solusi kakuatan anu dipercaya-dimana téknologi nyumponan kaamanan sareng efisiensi, nguatkeun pangiriman énergi anu langkung pinter.

630 kVA vpi transformer

 